You are here > Products > Medium Voltage Contact Us Site Map Login

 

 

 

 Model  FP07 FP12 FP24 FP36
16B 31D 31E 31F 16B 25D 25E 25F 16B 25D 25E 25F 16B 25D 25E 25F
 Type SF6 gas
 Rated Voltage(KV) 7.2 12 24 36
 Rated normal current(A) 630 1250 1600 2000 630 1250 1600 2000 630 1250 1600 2000 630 1250 1600 2000
Rated frequency(HZ) 50
Rated breaking current(KA) 18.4(3) 31.5(3) 31.5(3) 31.5(3) 16(3) 29(3) 29(3) 29(3) 16(3) 25(3) 25(3) 25(3) 16(3) 25(3) 25(3) 25(3)
Rated making current(KA) 46 80 80 80 40 73 73 73 40 63 63 63 40 63 63 63
 Power frequency withstand voltage (KV) 20 28 50 70
 Lightning impulse withstand voltage(KV) 60 75 125 170
Rated operating sequence  O-0.3SEC  -CO-3MIN-CO
 Installation Indoor
 Operating mechanism BLRM( Spring Type)
 Closing / Opening /  Breaking time(sec) 65-95/36-55/56-75
 Creepage distance (mm) 500
 Applicable standard IEC 62271-100

© 2005 Pars Switch - All Rights Reserved
Site produced by
Aminzadeh & CRM Group of PARS SWITCH